Bay controller - GBU200/Toshiba

Product selection

Hardware code

Software code


Hardware selection

Application of power system

Without CT/VT
CT/VT module with sensitive CT input (VCT51B) – CT x 4, CTsef x 1, VT x 6 (for BCPU)
CT/VT module with sensitive CT input (VCT51B) – CT x 4, CTsef x 1, VT x 6 (for BCPU) with power quality monitoring input (VCT54B)
CT/VT module (VCT52B) – CT x 4,VT x 5 (for BCU)
CT/VT module (VCT52B) – CT x 4,VT x 5 (for BCU) with power quality monitoring input (VCT55B)
CT/VT module for bus section or bus coupler bays (VCT53B) – CT x 4, VT x 7 (for BCU)
CT/VT module for bus section or bus coupler bays (VCT53B) – CT x 4, VT x 7 (for BCU) with power quality monitoring input (VCT56B)

DC rated voltage

110-250 Vdc (or 100-220 Vac)

24-60 Vdc

System Frequency

N/A

50Hz

60Hz

AC rated current

N/A

1A

5A

Outlines

Standard LCD, 1/3 size case; flush mounting type (IFU)

Standard LCD, 1/3 size case; rack mounting type (IFU)


Standard LCD, 1/2 size case; flush mounting type

Large LCD, 1/2 size case; flush mounting type

Standard LCD, 1/2 size case; rack mounting type

Large LCD, 1/2 size case; rack mounting type


Standard LCD, 3/4 size case; flush mounting type

Large LCD, 3/4 size case; flush mounting type

Standard LCD, 3/4 size case; rack mounting type

Large LCD, 3/4 size case; rack mounting type


Standard LCD, 1/1 size case; flush mounting type

Large LCD, 1/1 size case; flush mounting type

Terminal blocks for BIOs and PWS

Compression plug type

Ring type terminal

BI/BO modules

1×BIO module

2×BIO module

3×BIO module

4×BIO module

5×BIO module

6×BIO module

7×BIO module

8×BIO module

Communication port

Select port type


Software selection

Function block

Select functions

Protocol

IEC 61850

Language

English

Function table


Function Block Description Ordering No. (Position “G & T”)
BCU BCPU IFU
31
32
34
35
39
[Control function]
Control DPSY Double position control with synchronizing check
DPOS Double position device control
SPOS Single position device control
TPOS Three position device control
TAP TAP control (BCD)
TAP control (DCAI)
SOFTSW Software switch controller
Interlock ILK Interlock
AutoSEQ ASEQ Automatic sequential control
Monitoring -- Monitoring
-- DCB Double command blocking
-- DCAI Double command blocking (3) (3) (3) (3) (3)
-- DCAO DC analog output control (3) (3)
-- SYNDIF Synchrocheck between different network
-- MNOVR Manual override
[Protection]
50/67, 51/67 OC Non-directional / directional phase overcurrent protection (4 steps)
50N/67N, 51N/67N EF Non-directional / directional earth fault overcurrent protection (4 steps)
50SEF/ 51SEF SEF Non-directional sensitive overcurrent protection (2 steps)
46/67 OCN Non-Directional / directional negative sequence phase over-current protection (4 steps)
50BF CBF Circuit breaker failure protection (2 stages
37 UC Phase under-current protection (2 steps)
46BC BCD Broken conductor protection
49 THM Thermal overload protection
-- CLP Cold load protection
59 OV. OVS Phase over-voltage protection (4 steps)
59N OVG Earth fault over-voltage protection (4 steps)
47 OVN Negative sequence phase over-voltage protection (4 steps)
27 UV, UVS Phase under-voltage protection (4 steps)
81 FRQ Frequency protection (6 steps)
ROCOF DFRQ Rate of change of frequency (df/dt) (6 steps)
51V OCV Voltage controlled/restraint overcurrent (4 steps)
50SOTF SOTF-OC Switch on to fault protection
21FL FL Fault locator
-- ICD Inrush current detection function (2f)
79 ARC CB autoreclose function (three poles combined)
25 VCHK Voltage check for autoreclose
[Common]
Event -- Event and alarm
Measurement -- Measurement
Counter GCNT Counter function for the general
Communication -- Remote communication (4) (4) (4) (4) (4)
-- TCS Trip circuit supervision
-- VTF VTF detection function
-- CTF CTF detection function
-- PWRQTY Power quality monitoring (7) (7)
-- PLC Programmable logic controller

Note:

: Standard, : Equipped depending the hardware configuration
(1) Maximum controlling number for devices and tap-changes: DPSY: 2; DPOS: 72; TPOS: 24; SPOS: 20; TAP Control & measurement: 4; TAP Measurement only: 12; SOFTSW: 64
(2) That is, between transmission line and generator plant
(3) Function will be available when DCAI/DCAO modules are selected by the order at the ‘A’ and ‘B’ positions.
(4) ommunication is dependent on the selection of modules and protocols at ‘E’ and ‘F’’ positions.
(5) For programming, the user shall purchase a license ‘PE-261’ separately (see Optional accessories).
(6) When "MNOVR" is required, you shall select either 6, 7, 8, J or K (i.e., Large LCD) at “9” position of Hardware Selection
(7) “PWRQTY” is achieved with a special VCT selected with either 4, 5, or 6 at “7” position of Hardware Selection.